10.5 - Type I Memorization Sheet
Module: Universal Review and Mock Examinations
Purpose: One-page-target rapid review of the highest-priority Type I facts before Universal mock examinations
Covers: Type I material consolidated from Sections 7.1–7.8
Regulatory verification basis: Current Module 7 material verified August 11, 2026
Use: Memorize the classification, recovery, access, compressor-condition, and disposal rules below; return to Module 7 when a condition or exception is unclear
1. Type I = Small Appliances
A small appliance must satisfy all four conditions:
Fully manufactured at a factory
+
Factory charged
+
Hermetically sealed at a factory
+
5 lb or less of refrigerant
Fast Classification Rule
≤5 lb ALONE
≠
TYPE I
A field-connected residential split system with 4 lb of refrigerant is not automatically Type I because it does not meet the complete factory-manufactured / factory-charged / factory-sealed definition.
2. Common Type I Examples
Typical small appliances include:
- Household refrigerators.
- Household freezers.
- Room and window air conditioners.
- Portable air conditioners that meet the complete definition.
- Packaged terminal air conditioners.
- Packaged terminal heat pumps.
- Dehumidifiers.
- Under-the-counter ice makers.
- Vending machines.
- Drinking-water coolers.
Do Not Automatically Classify as Type I
- MVACs.
- MVAC-like appliances.
- Refrigerated-cargo systems.
- Field-assembled or field-connected equipment.
- Factory-sealed equipment containing more than 5 lb.
- Equipment that merely looks physically small.
EQUIPMENT SIZE
≠
TYPE I CLASSIFICATION
3. Type I Recovery Requirements
Current Recovery Table
| Recovery Condition | Required Result |
|---|---|
| Recovery/recycling equipment manufactured before November 15, 1993 | 80% recovery |
| Recovery/recycling equipment manufactured on or after November 15, 1993 + appliance compressor functional | 90% recovery |
| Recovery/recycling equipment manufactured on or after November 15, 1993 + appliance compressor not functional | 80% recovery |
| Alternative | Evacuate appliance to 4 in. Hg vacuum |
Memorize
POST-1993 EQUIPMENT
+
APPLIANCE COMPRESSOR WORKS
→ 90%
POST-1993 EQUIPMENT
+
APPLIANCE COMPRESSOR FAILED
→ 80%
PRE-1993 RECOVERY EQUIPMENT
→ 80%
ALTERNATIVE
→ 4 in. Hg vacuum
Exam Traps
- The date applies to the recovery/recycling equipment, not the appliance.
- The 80% / 90% decision uses the appliance compressor, not the recovery-machine compressor.
- Type I 80% recovery is not the same concept as the 80% recovery-cylinder fill reminder.
4. Functional Versus Failed Compressor
Operating Compressor
With system-dependent recovery:
OPERATE THE APPLIANCE COMPRESSOR
The compressor helps move refrigerant:
low side
→ compressor
→ high side
→ recovery connection
High-priority Type I operating-compressor concept:
OPERATING COMPRESSOR
→ conventional high-side recovery
Useful aids when appropriate:
- Controlled warming.
- Defrost heater, if equipped and permitted.
- Allowing trapped liquid to vaporize.
Failed Compressor
If the appliance compressor does not operate:
NO COMPRESSOR PUMPING ASSISTANCE
High-priority failed-compressor concept:
ACCESS HIGH SIDE
+
ACCESS LOW SIDE
Both-side access helps overcome:
- Capillary-tube restriction.
- Slow pressure equalization.
- Refrigerant trapped in the compressor shell and oil.
- Refrigerant trapped in cold heat exchangers or tubing pockets.
Helpful Type I exam techniques include:
- Controlled heat.
- Carefully tapping / sharply striking the compressor as taught in the Type I recovery procedure.
- Defrost heater if equipped and permitted.
- The special vacuum-pump / nonpressurized recovery container example taught for the failed-compressor case.
Never use an open flame to heat the appliance or compressor.
Fast Comparison
| Item | Compressor Works | Compressor Failed |
|---|---|---|
| Appliance compressor assists recovery | Yes | No |
| Type I system-dependent emphasis | Operate compressor | Do not depend on compressor |
| Access emphasis | High-side recovery may be sufficient in the taught operating-compressor method | High + low side |
| Post-1993 percentage | 90% | 80% |
| Controlled heat / trapped refrigerant | May help | Especially important |
| 4 in. Hg vacuum alternative | Available | Available |
5. Access Fittings and Process Stubs
Process Stub
PROCESS STUB
→ length of tubing
→ provides refrigerant access
→ can be resealed after service
A process stub is not a valve.
Piercing / Solderless Access Fitting
PIERCING ACCESS VALVE
→ clamp-on temporary access fitting
Before installation, consider:
- Tubing diameter.
- Tubing material.
- Tubing condition.
- Fitting design.
- Manufacturer instructions.
Do not choose:
- Capillary tube.
- Sharp bend.
- Crushed section.
- Corroded section.
- Brazed joint.
End-of-Service Rule
Current Type I test-topic emphasis:
SOLDERLESS ACCESS FITTING
→ REMOVE AT CONCLUSION OF SERVICE
→ RESTORE / RESEAL TUBING
→ LEAK CHECK
Access-Fitting Exam Traps
PROCESS STUB
≠
PIERCING VALVE
TEMPORARY ACCESS FITTING
≠
PERMANENT REPAIR
ACCESS FITTING
≠
RECOVERY EQUIPMENT
Prepare the recovery setup before creating controlled refrigerant access so avoidable release is minimized.
6. Self-Contained Recovery
SELF-CONTAINED RECOVERY MACHINE
→ has its own independent recovery compressor / pumping means
Key reminders:
- Use an approved recovery cylinder.
- Confirm refrigerant compatibility.
- Avoid refrigerant cross-contamination.
- Monitor recovery-machine discharge pressure.
- Control cylinder pressure / temperature safely.
- Follow the recovery-machine and cylinder instructions for port selection and setup.
Do Not Confuse
SELF-CONTAINED RECOVERY MACHINE
≠
VACUUM PUMP
A vacuum pump is normally an evacuation/dehydration tool.
7. Type I Service Sequence
For ordinary service:
CLASSIFY APPLIANCE
→ IDENTIFY REFRIGERANT
→ IDENTIFY SERVICE ACTIVITY
→ DETERMINE COMPRESSOR CONDITION
→ CHOOSE RECOVERY METHOD
→ REACH TYPE I ENDPOINT
→ PERFORM REPAIR
→ LEAK CHECK
→ EVACUATE / DEHYDRATE AS APPROPRIATE
→ RECHARGE
→ VERIFY OPERATION
Compressor Replacement
COMPRESSOR REPLACEMENT
→ RECOVER REFRIGERANT FIRST
→ THEN OPEN CIRCUIT
A failed compressor changes the recovery technique.
It does not eliminate the recovery requirement.
8. Type I Disposal
Service Versus Disposal
REPAIR + RETURN TO SERVICE
→ TYPE I SERVICE RULES
END OF USEFUL LIFE
→ SAFE-DISPOSAL RULES
Small-Appliance Disposal Certification Exception
For refrigerant recovery performed solely for disposal of a small appliance:
TECHNICIAN-CERTIFICATION EXCEPTION MAY APPLY
but:
RECOVERY REQUIREMENT REMAINS
+
COMPLIANT RECOVERY EQUIPMENT REMAINS REQUIRED
+
VENTING PROHIBITION REMAINS
The disposal exception does not authorize uncertified compressor replacement or other ordinary service.
9. Final Processor: Recover or Verify
For a small appliance entering final disposal:
FINAL PROCESSOR
→ RECOVER remaining refrigerant
OR
→ VERIFY acceptable prior recovery
Prior-Recovery Signed Statement
Memorize:
NAME
+
ADDRESS
+
DATE
A sticker alone is not sufficient EPA verification.
Qualifying Contract
REGULAR COMMERCIAL SUPPLIER
→ qualifying contract pathway may be used
The contract alternative is not intended for an occasional individual consumer drop-off.
If Refrigerant Already Leaked Out
A leaked-out statement may apply when the refrigerant loss resulted from:
SYSTEM FAILURE
ACCIDENT
UNAVOIDABLE OCCURRENCE
It does not apply to:
DELIBERATE LINE CUTTING
INTENTIONAL / NEGLIGENT RELEASE
Final-Processor Record Retention
SIGNED STATEMENTS / CONTRACTS
→ KEEP 3 YEARS
Do not confuse this with the separate technician disposal-record range:
>5 lb and <50 lb
A Type I small appliance contains:
≤5 lb
so that separate mid-sized-appliance technician record range normally does not apply to Type I small appliances.
10. Type I Numbers to Know Cold
| Number / Date | Type I Meaning |
|---|---|
| 5 lb or less | Maximum charge in the complete small-appliance definition |
| November 15, 1993 | Recovery/recycling-equipment date boundary |
| 90% | Post-1993 recovery equipment + functional appliance compressor |
| 80% | Pre-1993 equipment, or post-1993 equipment + nonfunctional appliance compressor |
| 4 in. Hg vacuum | Alternative Type I recovery endpoint |
| 3 years | Final processor keeps required signed statements / contracts |
11. Highest-Priority Type I Exam Traps
Trap 1
≤5 lb
→ automatically Type I
Wrong. Use all four small-appliance conditions.
Trap 2
Appliance manufacture date
→ determines 80% / 90%
Wrong. The date belongs to the recovery/recycling equipment.
Trap 3
Recovery-machine compressor works
→ 90%
Wrong. The condition concerns the appliance compressor.
Trap 4
Failed compressor
→ no recovery required
Wrong. Technique changes; recovery remains required.
Trap 5
Failed compressor
→ use only high-side access
Wrong for the taught Type I failed-compressor concept. Use both high- and low-side access.
Trap 6
Piercing valve
→ process stub
Wrong. Stub = tubing; piercing valve = temporary access device.
Trap 7
Leave solderless access fitting installed permanently
Wrong for current Type I exam emphasis. Remove it after service and restore the tubing.
Trap 8
Disposal certification exception
→ permission to vent
Wrong.
Trap 9
Sticker on appliance
→ sufficient prior-recovery verification
Wrong.
Trap 10
Deliberately cut lines
→ leaked-out exception
Wrong.
12. Type I Final Memory Map
TYPE I
→ SMALL APPLIANCE
FACTORY MANUFACTURED
+
FACTORY CHARGED
+
HERMETICALLY SEALED
+
≤5 lb
POST-1993 + COMPRESSOR WORKS
→ 90%
POST-1993 + COMPRESSOR FAILED
→ 80%
PRE-1993 RECOVERY EQUIPMENT
→ 80%
ALTERNATIVE
→ 4 in. Hg vacuum
OPERATING COMPRESSOR
→ high-side recovery emphasis
FAILED COMPRESSOR
→ high + low access
→ controlled heat / trapped-refrigerant techniques
PROCESS STUB
→ tubing
PIERCING / SOLDERLESS FITTING
→ temporary
→ remove after service
→ reseal + leak check
FINAL PROCESSOR
→ recover
OR
→ verify prior recovery
SIGNED STATEMENT
→ NAME + ADDRESS + DATE
REQUIRED DISPOSAL RECORDS
→ 3 YEARS
References
Project Source Sections
- Section 7.1 - Small Appliance Definition and Examples
- Section 7.2 - Type I Exclusions and Boundary Cases
- Section 7.3 - Type I Recovery Requirements
- Section 7.4 - Access Fittings and Process Stubs
- Section 7.5 - Recovery with an Operating Compressor
- Section 7.6 - Recovery with a Failed Compressor
- Section 7.7 - Self-Contained Recovery
- Section 7.8 - Type I Service and Disposal Scenarios
- Section 7.9 - Quick Reference
- Section 10.1 - Universal Certification Comparison Tables
- Section 10.2 - High-Priority Numbers and Thresholds
- Section 10.3 - Commonly Confused Terms